Description
Dynamic self-checking flame detector used with R7861 Dynamic
Self-check Amplifiers for sensing the ultraviolet radiation
generated by the combustion of gas, oil, or other fuels.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
sensor to provide the UV sensor tube checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral
locating reference points to assure proper operation of the shutter
mechanism.
• Field replaceable ultraviolet sensing tube and quartz viewing window.
• Models with threaded conduit fitting and color-coded leadwires allow
rapid electrical installation.
• C7061A1046 5 pin Brad Harrison type (formally 41307N) mating
connector not supplied nor available through Honeywell.
• Two detectors can be wired in parallel to reduce nuisance shutdowns
in difficult flame sighting applications.
• Protective heat block built into mounting flange.
• -40°F (-40°C) rated ultraviolet sensing tube is supplied.
• C7061E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7061F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
• Pipe connection (all models) 1 in. NPT, includes 1 in. to 3/4 in.
bushing adapter for 3/4 in. viewing pipe mounting.








There are no reviews yet.