Honeywell Pilot Burners- Module Q179A1001/U Flame Rectifier Gas Pilots
- Application: For Intermittent or Interrupted Ignition
- Orifice: 0.025 in. dia. (0.635 mm dia.)
- Wiring Terminal Type: Rajah
- Tip Style: I
- Includes: Flame electrode and ignition electrode
- Used With: Q624 or other suitable ignition transformer.
Honeywell Pilot Gas Valve Control- V4046C1054/U Valve Module
- Pipe Size (inch): 3/8 in.
- Capacity (cfh): 67 cfh
- Capacity (m3/hr): 1.90 m3/hr
- Voltage: 110 Vac; 120 Vac
- Frequency: 50 Hz; 60 Hz
- Electrical Connections: Two 36-in. leadwires and 1/2 in. conduit bushing
- Approvals, Swiss RE: Acceptable
Honeywell Pilot Gas Valve Control- V4046C1120/U Reliable Valve Module
- Pipe Size (inch): 3/8 in.
- Capacity (cfh): 67 cfh
- Capacity (m3/hr): 1.90 m3/hr
- Voltage: 120 Vac
- Frequency: 60 Hz
- Electrical Connections: Two 10 ft. leadwires and 1/2 in. conduit bushing
- Approvals, Swiss RE: Acceptable
Honeywell Pilot Gas Valve Control- V8046C1014/U Valve Module
- Pipe Size (inch): 1/4 in.
- Capacity (cfh): 20 cfh
- Capacity (m3/hr): 0.57 m3/hr
- Voltage: 24 Vac
- Frequency: 60 Hz
- Electrical Connections: Two 36-in. leadwires and 1/2 in. conduit bushing
Honeywell Pilot Gas Valve Control- V8046C1030/U Reliable Valve Module
- Pipe Size (inch): 3/8 in.
- Capacity (cfh): 67 cfh
- Capacity (m3/hr): 1.90 m3/hr
- Voltage: 24 Vac
- Frequency: 60 Hz
- Electrical Connections: Two 36-in. leadwires and 1/2 in. conduit bushing
Honeywell Pilot Gas Valves Module- V4046C1005/U- Gas Valve Control
- Pipe Size (inch): 1/8 in.
- Capacity (cfh): 20 cfh
- Capacity (m3/hr): 0.57 m3/hr
- Voltage: 110 Vac; 120 Vac
- Frequency: 50 Hz; 60 Hz
- Electrical Connections: Two 36-in. leadwires and 1/2 in. conduit bushing
- Approvals, Swiss RE: Acceptable
Honeywell Pilot Gas Valves Module- V4046C1021/U- Gas Valve Control
- Pipe Size (inch): 1/4 in.
- Capacity (cfh): 20 cfh
- Capacity (m3/hr): 0.57 m3/hr
- Voltage: 110 Vac; 120 Vac
- Frequency: 50 Hz; 60 Hz
- Electrical Connections: Two 36-in. leadwires and 1/2 in. conduit bushing
- Approvals, Swiss RE: Acceptable
Honeywell Pressure & Limit Controller L4079W1000/U – Pressuretrol® Model
- Application: High oil pressure limit switch for heavy oil applications.
- Operating Range (psi): 10 to 150 psi; 225 psi - Maximum Sustained
- Operating Range (kPa): 35 to 350 kPa; 1151 kPa - Maximum Sustained
- Switch Operation: Manual Reset
- Switching Action: SPST break on pressure rise- Oil Applications
Honeywell Pressure and Limit Controller L404F1227/U – Pressuretrol® Type
- Operating Range (psi): 10 to 150 psi
- Operating Range (kPa): 69 to 1034 kPa
- Maximum Sustained Pressure (psi): 225 psi
- Maximum Sustained Pressure (kPa): 1151 kPa
- Differential Pressure Range (psi): 10 to 22 psi
- Differential Pressure Range (kPa): 60 to 152 kPa
- Switching Action: SPDT snap action, make R-W, break R-B on pressure rise
- Includes: BSPT ground screw and European Enclosure
Honeywell Pressure and Limit Controller L4079B1033/U – Pressuretrol® Series
- Application: Provide limit control of steam, air, non-combustible gases or non-corrosive fluids
- Operating Range (psi): 2 to 15 psi; 25 psi - Maximum Sustained
- Operating Range (kPa): 14 to 103 kPa; 172 kPa - Maximum Sustained
- Switch Operation: Manual Reset
- Switching Action: SPST break on pressure rise
Honeywell Pressure and Limit Controllers- L4079A1035/U Pressuretrol® Limit Controller
- Application: Provide limit control of steam, air, non-combustible gases or non-corrosive fluids
- Operating Range (psi): 2 to 15 psi; 25 psi - Maximum Sustained
- Operating Range (kPa): 14 to 103 kPa; 172 kPa - Maximum Sustained
- Switch Operation: Manual Reset
- Switching Action: SPST (two) break simultaneously on pressure rise
Honeywell Pressure Regulating Gas Valves Two Stage Diaphragm- V8944N1046/U Module
- Type of Fuel: Natural
- Pipe Size (inch): 2 in.
- Pipe Size (DN): DN50
- Opening Characteristics: Rapid Opening 2-stage
- Valve Opening Time: 6 sec max
- Pressure Regulator Setpoint (in. wc): Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc
- Comments: (3) 30" leadwires
Honeywell Pressure Regulating- V8944N1053/U Two Stage Diaphragm Gas Valves
- Type of Fuel: Natural
- Pipe Size (inch): 1 in.
- Pipe Size (DN): DN25
- Opening Characteristics: Rapid Opening 2-stage
- Valve Opening Time: 6 sec max
- Pressure Regulator Setpoint (in. wc): Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.2 in. wc; Factory Setting, High Fire – 3.5 in. wc
- Comments: (3) 30" leadwires
Honeywell Pressure Safety Switch Reliable Control- C6097A3038/U Module
- Adjusting range * in WC (mbar): 12 - 60 in. wc 30 - 150 mbar
- Difference between switching pressure and possible reset: 0.8 - 4.8 in. wc 2 - 12 mbar
- Differential type: Additive
- Switch Operation: Manual Reset
- Switch Action at Setpoint: Breaks NO to COM on pressure fall.
Honeywell Pressure Safety Switch Reliable Control- C6097B3002/U Module
- Adjusting range * in WC (mbar): 12 to 60 in. wc 30 - 150 mbar
- Difference between switching pressure and possible reset: 0.8 - 4.8 in. wc 2 - 12 mbar
- Differential type: Subtractive
- Switch Operation: Manual Reset
- Switch Action at Setpoint: Breaks NC to COM on pressure rise.
Honeywell Pressure Safety Switch Reliable Control- C6097B3028/U Module
- Adjusting range * in WC (mbar): 1 to 20 in. wc 2,5 - 50 mbar
- Difference between switching pressure and possible reset: 0.4 - 0.8 in. wc 1 - 2 mbar
- Differential type: Subtractive
- Switch Operation: Manual Reset
- Switch Action at Setpoint: Breaks NC to COM on pressure rise.
Honeywell Pressuretrol® Controller L404F1094/U – Pressure & Limit Control
- Operating Range (psi): 20 to 300 psi
- Operating Range (kPa): 138 to 2068 kPa
- Maximum Sustained Pressure (psi): 350 psi
- Maximum Sustained Pressure (kPa): 2413 kPa
- Differential Pressure Range (psi): 20 to 50 psi
- Differential Pressure Range (kPa): 138 to 345 kPa
- Switching Action: SPDT snap action, make R-W, break R-B on pressure rise
Honeywell Pressuretrol® Controller L404F1391/U – Pressure & Limit Control
- Operating Range (psi): 20 to 300 psi
- Operating Range (kPa): 140 to 2070 kPa
- Maximum Sustained Pressure (psi): 350 psi
- Maximum Sustained Pressure (kPa): 2413 kPa
- Differential Pressure Range (psi): 20 to 50 psi
- Differential Pressure Range (kPa): 140 to 345 kPa
- Switching Action: Snap switch makes R-W on pressure rise
- Includes: Miss-wiring Compliant (less B terminal)
Honeywell Pressuretrol® L404F1375/U Controller – Durable Pressure & Limit Control
- Operating Range (psi): 5 to 50 psi
- Operating Range (kPa): 35 to 350 kPa
- Maximum Sustained Pressure (psi): 85 psi
- Maximum Sustained Pressure (kPa): 586 kPa
- Differential Pressure Range (psi): 6 to 14 psi
- Differential Pressure Range (kPa): 40 to 100 kPa
- Switching Action: Snap switch makes R-W on pressure rise
- Includes: Miss-wiring Compliant (less B terminal)
Honeywell Pressuretrol® L404F1409/U Controller – Durable Pressure & Limit Control
- Operating Range (psi): 2 to 15 psi
- Operating Range (kPa): 14 to 103 kPa
- Maximum Sustained Pressure (psi): 25 psi
- Maximum Sustained Pressure (kPa): 172 kPa
- Differential Pressure Range (psi): 2 to 6 psi
- Differential Pressure Range (kPa): 15 to 40 kPa
- Switching Action: Snap switch makes R-W on pressure rise
- Includes: Miss-wiring Compliant (less B terminal)
Honeywell Proportional Pressuretrol® L91B1050/U – Reliable Pressure & Limit Control
- Operating Range (psi): 5 to 150 psi; 225 psi - Maximum Sustained
- Operating Range (kPa): 34 to 1034 kPa; 1151 kPa - Maximum Sustained
- Differential Pressure Range (psi): 5 to 23 psi
- Differential Pressure Range (kPa): 35 to 160 kPa
- Mounting: optional surface mount through back of case
- Sensor Element: Brass bellows
- Approximate, Dimensions: 5 3/4 in. high x 4 1/2 in. wide x 2 3/4 in. deep (146 mm high x 114 mm wide x 70 mm deep)
- Modulation Output: Single potentiometer, 140 ohms
Honeywell Proportional Pressuretrol® L91B1118/U Module- Accurate Pressure & Limit Control
- Operating Range (psi): 10 to 300 psi; 325 psi - Maximum Sustained
- Operating Range (kPa): 0 - 2 MPa; 2241 kPa - Maximum Sustained
- Differential Pressure Range (psi): 28 to 110 psi
- Differential Pressure Range (kPa): 193 to 758 kPa
- Mounting: 1/4 in BSP-TR thread Mounting
- Sensor Element: Phos-bronze bellows
- Approximate, Dimensions: 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep)
- Modulation Output: Single potentiometer, 140 ohms
Honeywell Q179A1035/U Flame Rectifier Gas Pilot – Pilot Burner Module
- Application: For Intermittent or Interrupted Ignition
- Orifice: 0.025 in. dia. (0.635 mm dia.)
- Wiring Terminal Type: Rajah
- Tip Style: 45 degree right hand
- Includes: Flame electrode and ignition electrode
- Used With: Q624 or other suitable ignition transformer.
Honeywell Q179A1076/U Pilot Burner Flame Rectifier Module
- Application: For Intermittent or Interrupted Ignition
- Orifice: 0.028 in. dia. (0.711 mm dia.)
- Wiring Terminal Type: Rajah
- Tip Style: 45 degree Y
- Includes: Flame electrode and ignition electrode
- Used With: Q624 or other suitable ignition transformer.
Honeywell Q179A1092/U Flame Rectifier Gas Pilot | Pilot Burner Module
- Application: For Intermittent or Interrupted Ignition
- Orifice: 0.028 in. dia. (0.711 mm dia.)
- Wiring Terminal Type: Rajah
- Tip Style: 45 degree T
- Includes: Flame electrode and ignition electrode
- Used With: Q624 or other suitable ignition transformer.
Honeywell Q179A1126/U Pilot Burner Module – Reliable Flame Rectifier
- Application: For Intermittent or Interrupted Ignition
- Orifice: 0.025 in. dia. (0.635 mm dia.)
- Wiring Terminal Type: Screw Terminal
- Tip Style: I
- Includes: Flame electrode and ignition electrode with screw terminal connections
- Used With: Q624 or other suitable ignition transformer.
Honeywell Q7800A1005/U 22 Terminal Universal Wiring Subbases 7800 Series Burner Controls
- Application: Wiring Subbase
- Approximate, Dimensions: 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep)
- Weight lb. (kg): 7 oz (0.20 kg)
- Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2.
- Used With: Panel mount
Honeywell Q7800B1003/U 22 Terminal Universal Wiring Subbases 7800 Series Burner Controls
- Application: Wiring Subbase
- Approximate, Dimensions: 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep)
- Weight lb. (kg): 1 lb 3 oz (0.54 kg)
- Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2.
- Used With: Burner/wall mount 2 knockouts each end